Thermon KSR-SK-DB Uživatelský manuál Strana 2

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 6
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 1
2
KSR-SK-DB In-Line Splice Kit
Tools Required . . .
The following installation procedures are suggested guidelines for
the installation of in-line cable splices. They are not intended to
preclude the use of other methods and good engineering or field
construction practices.
Receiving, Storing and Handling . . .
1. Inspect materials for damage incurred during shipping.
2. Report damages to the carrier for settlement.
3. Identify parts against the packing list to ensure the proper
type and quantity has been received.
4. Store in a dry location.
Installation Precautions . . .
To minimize the potential for arcing and fire caused by product
damage or improper installation use ground-fault protection. The
National Electrical Code (NEC) and Canadian Electrical Code (CEC)
require ground-fault protection of equipment for each branch
circuit supplying electric heat tracing.
Installation must comply with Thermon requirements and be in-
stalled in accordance with the NEC, CEC, or any other applicable
national and local codes.
Power connections and end termination must be located in NEMA 4
or 4X enclosures (Thermon KSR-JB or UL Listed equivalent) located
above moisture line.
De-energize all power sources before opening enclosure.
Keep ends of heating cable and kit components dry before and
during installation.
Do not locate the splice in an expansion joint area, where a bend
occurs in the cable, or within a conduit entering or exiting a slab.
Do not splice cables that have different catalog numbers and/or
voltage ratings.
Component approvals and performance rating are based on use
of Thermon specified parts only.
The kit instructions should be used in conjunction with the
installation instruction for the heating cable and other accessary
items.
KSR-SK-DB
1
2
Item Quantity Description
1 1 Heat Shrink 28mm X 325mm (1.10” X 12.80”)
2 1 Heat Shrink 20mm X 120mm (.79” X 4.72”)
3 & 4 1
Heat Shrink 10mm X 125mm (.39” X 4.92”)
Cut heat shrink into 3 pieces per step 11
5 1 RTV Tube
6 2 Small Lug (14-16 AWG)
7 1 Large Lug (10-12AWG)
8 2 Power Connection Boot
9 1 Mastic Tape 25 mm X 150MM (.98” X 5.91”)
3
Kit Contents . . .
Canadian Standard Association
Certified Snow Melting Equipment
for Applications Having a Type
Designation of 2B
Underwriters Laboratories Inc.
5N23 De-Icing and Snow Melting
Equipment (KOBQ)
4
5
6 7
8
9
3
Zobrazit stránku 1
1 2 3 4 5 6

Komentáře k této Příručce

Žádné komentáře