Installation InstructionsCKTESTMPETK-10 & PETK-11Connection KitTo be used with *Thermon Europe Series Cables This equipment is tested and app
Connection kit CKTES (Connection Kit Thermon Series Cable) is designed to connect a cold lead cable to a series constant watt heating cable or to repa
Kit Contents 2Tools Required 16423589107Form TEP0107U-0512 © Thermon Manufacturing Co. Information subject to change.CKT
Details Of Cold Lead And Lug Sizes 3Form TEP0107U-0512 © Thermon Manufacturing Co. Information subject to change.In-Line Connectio
Step 1First determine the correct circuit length, then slide the screw cap and the rubber grommet over the heating cable and cold lead cable (in case
Step 5 Insert the bare conductor of both the Cold Lead/Heating Cable and Heating Cable into the crimp connector and ensure complete overlap of conduct
Step 8Mount the CKTES/PETK on a at surface, with expansion loop of 150 mm in the cables. Heating Cable/Cold Leads and joint secured in place using b
Installation Instructions for Power Termination 7DescriptionPower and End Termination Kit PETK for Thermon TESH series constant watt heatin
Step 3Cut and remove (10 mm) primary insulation jacket to reveal the bare conductor.Step 4Slide green/yellow ground sleeve over twisted braid. Crimp c